F gas refrigerant emissions are leaks of fluorinated gases, such as HFCs, from air conditioning, refrigeration and heat pumps. If you own or control the equipment, they are Scope 1 fugitive emissions. Calculate them as kilograms of refrigerant lost multiplied by that gas’s conversion factor, such as 1,924 kg CO2e per kg for R410A under the DESNZ 2026 set.
Refrigerant is the Scope 1 source most often missed in SME footprints. It does not appear on an energy bill, and the quantities look tiny. But many HFCs have global warming potentials in the thousands, so a routine top-up of a few kilograms can outweigh a year of electricity at a small office.
This article explains where refrigerant sits in a footprint, the two calculation methods in the government’s guidance, the leak-check rules under the F gas regulation and what is changing.
Why are refrigerant leaks counted in Scope 1?
The GHG Protocol Corporate Standard lists fugitive emissions as a category of direct emissions. It describes them as intentional or unintentional releases, including equipment leaks from joints, seals, packing and gaskets, and HFC emissions during the use of refrigeration and air conditioning equipment. Our explainer on https://auditmycarbon.com/what-is-a-carbon-footprint/ covers how Scope 1 fits into the whole picture.
The government’s environmental reporting guidelines take the same line. If you own or control the equipment, report the emissions under Scope 1. If you benefit from equipment controlled by someone else, such as a landlord’s central chiller, the emissions may fall into your Scope 3 instead.
Ownership matters, so check your leases and service contracts before deciding where each unit belongs. The test is whether your organisation controls the equipment, not who manufactured or services it.

How much does each refrigerant count for?
Each refrigerant has a conversion factor equal to its global warming potential. The >DESNZ 2026 conversion factors include these values in kg CO2e per kg released:
| Refrigerant | Common use | kg CO2e per kg |
|---|---|---|
| R404A | Commercial refrigeration | 3,943 |
| R410A | Split and VRF air conditioning, heat pumps | 1,924 |
| R407C | Older air conditioning | 1,624 |
| HFC-134a (R134a) | Chillers, vehicle air conditioning | 1,300 |
| HFC-32 (R32) | Newer split air conditioning | 677 |
| R290 (propane) | Small refrigeration, some heat pumps | 0.06 |
DESNZ’s methodology explains that these values mostly use GWPs from the IPCC Fifth Assessment Report (AR5), and have been held constant since the 2023 release. Blends are calculated from their components. R404A, for example, is 44% HFC-125, 52% HFC-143a and 4% HFC-134a, which gives 3,943.
How do you calculate refrigerant emissions?
The government’s >environmental reporting guidelines, last updated in March 2019, set out two methods in Annex C.
Simplified material balance method
This uses your actual service records, so it is the more accurate option. Emissions in kg of refrigerant are:
- refrigerant used to charge new equipment, minus the full capacity of that new equipment
- plus refrigerant used to service existing equipment, on the basis that top-ups replace what leaked
- plus the full capacity of equipment retired, minus the refrigerant recovered from it
Multiply the result by the conversion factor for each gas, and calculate each refrigerant separately.
Worked example: material balance
An office business has several R410A air conditioning systems. Its service company’s records for the year show:
- 6.5 kg of R410A added during servicing
- one unit with an 8.0 kg charge was decommissioned, and 7.2 kg was recovered
- no new equipment was charged on site
Refrigerant lost: 6.5 + (8.0 − 7.2) = 7.3 kg
Emissions: 7.3 kg × 1,924 = 14,045 kg CO2e, or about 14.0 tCO2e
For comparison, at the DESNZ 2026 UK electricity factor of 0.13096 kg CO2e per kWh, 14,045 kg CO2e is the same as about 107,000 kWh of grid electricity. That is why refrigerant deserves a line in every footprint.
Screening method
If you have no service records, the guidelines offer a screening method using default rates. You multiply the number of units, the charge, the years in use, a default annual leak rate and the GWP. Default annual leak rates in the guidelines include 3% for small stationary air conditioning, 6% for medium stationary air conditioning and heat pumps, and 17% for centralised supermarket refrigeration.
For three medium air conditioning units holding 8 kg of R410A each, used all year:
3 × 8 kg × 1 year × 6% × 1,924 = 2,771 kg CO2e
The guidelines warn that these defaults carry a high degree of uncertainty. If refrigerant turns out to be significant compared with your other sources, move to the material balance method.
What are the UK F gas leak-check rules?
Carbon reporting and legal compliance are separate duties, but they use the same data. In Great Britain, the F gas regulation sets leak-check frequencies based on the CO2-equivalent of the gas in each piece of equipment. Northern Ireland remains part of the EU F gas system.
The GOV.UK guidance on >checking F gas equipment for leaks sets out:
| CO2e in the equipment | Minimum check frequency | R410A equivalent | R404A equivalent |
|---|---|---|---|
| 5 to under 50 tonnes | Every 12 months | 2.4 kg | 1.3 kg |
| 50 to under 500 tonnes | Every 6 months | 24 kg | 13 kg |
| 500 tonnes or more | Automatic leak detection must be fitted; older switchgear needs checks every 3 months | 240 kg | 127 kg |
Fitting automatic leak detection doubles the allowed interval between checks. If a leak is found, it must be repaired as soon as possible and the check repeated within a month. Hermetically sealed systems under 10 tonnes CO2e do not have a maximum interval between checks. Failing to carry out checks or fix leaks can lead to a civil penalty.
Note that the kilogram thresholds on GOV.UK are calculated using the GWPs in the F gas regulation. These differ slightly from the AR5-based DESNZ reporting factors. Use the GOV.UK thresholds for compliance and the DESNZ factors for your carbon footprint.
For example, a system holding 30 kg of R410A is above the 24 kg line, so it needs checking at least every 6 months, or every 12 months with automatic leak detection.
What is happening to HFCs in Great Britain?
The F gas regulation limits the quantity of HFCs that can be placed on the market in Great Britain through a phasedown schedule. Defra consulted from 5 November to 17 December 2025 on tightening it. The proposal was to replace the current target of a 79% reduction by 2030 with a 98.6% reduction by 2048, adding steps from 2030 to 2050.
In a >May 2026 update on the consultation, Defra said further work is needed. It confirmed it will not legislate in 2026 to change the phasedown steps from 1 January 2027, so the existing step continues to apply for 2027. It still intends to reform the phasedown and plans to publish a summary of responses and next steps later in 2026.
For businesses, the direction is clear even if the dates are not. High-GWP refrigerants are likely to become scarcer and more expensive to service, which strengthens the case for lower-GWP equipment at replacement time.
How can you reduce refrigerant emissions?
- Keep an asset register with every unit’s refrigerant, charge and service history.
- Get leak checks done on time and fix leaks promptly. This is a legal duty and your cheapest reduction.
- Ask for kg figures on every service report. Without them you are stuck with the screening method.
- Plan replacements around lower-GWP refrigerants, as the GWP table above shows how large the difference can be.
- Check heat pump projects. A heat pump can cut gas use, but it brings refrigerant into your Scope 1, so choose the refrigerant carefully.
Our list of quick wins to reduce business carbon emissions includes other low-cost measures. To see refrigerant alongside your energy emissions, use our business carbon footprint calculator. If you want your refrigerant records turned into a defensible Scope 1 figure, you can book a carbon audit with us.
FAQ
Are refrigerant leaks Scope 1 or Scope 3?
They are Scope 1 if your organisation owns or controls the equipment. If the equipment is controlled by someone else, such as a landlord, the emissions may be Scope 3 for you.
What GWP should I use for R410A?
For carbon reporting in the UK, use the DESNZ conversion factor, which is 1,924 kg CO2e per kg in the 2026 set. The F gas leak-check thresholds on GOV.UK use the regulation’s own GWPs, so the kg thresholds are calculated slightly differently.
Do I need to report refrigerant emissions under SECR?
Quoted companies must report all material emissions from direct sources, which can include refrigerant leaks. Large unquoted companies report energy use and energy-related emissions, but refrigerant still belongs in a full GHG Protocol Scope 1 inventory.
How do I find out how much refrigerant leaked?
Ask your service company for the kg of refrigerant added and recovered at each visit. Top-ups are treated as replacing what leaked, which is the basis of the material balance method.
Is the HFC phasedown changing in 2027?
Not in 2027. Defra confirmed in May 2026 that it will not legislate in 2026 to change the phasedown steps from 1 January 2027, although it still plans wider reform.
Sources
- GHG Protocol, Corporate Accounting and Reporting Standard, revised edition (ghgprotocol.org)
- >DESNZ, Greenhouse gas reporting conversion factors 2026, and 2026 methodology report, section 4 (GOV.UK)
- >DESNZ, Environmental reporting guidelines, including SECR requirements, March 2019, Annex C (GOV.UK)
- >Environment Agency and Defra, Checking F gas equipment for leaks (GOV.UK)
- >Defra, Amending the hydrofluorocarbon phasedown schedule: consultation and May 2026 update (GOV.UK)
- Regulation (EU) No 517/2014 on fluorinated greenhouse gases, as it applies in Great Britain (legislation.gov.uk)
